Duct Static Pressure

Static pressure measured in the supply air duct, typically 2/3 of the way down the longest duct run. Primary control input for supply fan speed in VAV systems.

Brick

Supply_Air_Static_Pressure_Sensor

Category

pressures

Typical Range

-

Object Type

-

Haystack

Tags

dischargeMarkerductMarkerstaticMarkerpressureMarkersensorMarkerpointMarker

Kind

Number

Point Function

sensor

Haystack Unit

inH₂O

Source Units

inWC / Pa

States

-

Aliases

Common

Common Misspellings

duct-stactic-pressure

Notes

  • Typical setpoint for VAV systems is 1.0-2.0 inWC
  • ASHRAE Guideline 36 recommends static pressure reset based on VAV box damper positions
  • Sensor location at 2/3 point of the longest duct run is the industry standard
  • Low duct static with fan at full speed may indicate duct leakage or obstruction