Duct Static Pressure Setpoint

Target static pressure in the supply duct. Primary setpoint for supply fan speed control in VAV systems.

Brick

Supply_Air_Static_Pressure_Setpoint

Category

setpoints

Typical Range

-

Object Type

-

Haystack

Tags

dischargeMarkerductMarkerstaticMarkerpressureMarkerspMarkerpointMarker

Kind

Number

Point Function

setpoint

Haystack Unit

inH₂O

Source Units

inWC / Pa

States

-

Aliases

Common

Common Misspellings

duct-stactic-pressure-sp

Notes

  • Typical initial setpoint is 1.0-2.0 inWC for medium-pressure ductwork
  • ASHRAE Guideline 36 recommends static pressure reset — lower setpoint when VAV boxes are satisfied, raise when boxes are starved
  • Static pressure reset can save 20-40% of fan energy